Perkins UK 100 kVA / 80 kW diesel generator – typical specifications
Specification details
Generator rating 100 kVA / 80 kW
Prime power 100 kVA / 80 kW
Standby power 110 kVA / 88 kW (typical)
Power factor 0.8
Frequency 50 Hz
Rated voltage 400/230 V, 3 phase, 4 wire
Rated current approximately 144 A
Rated speed 1500 RPM
Engine brand Perkins UK
Engine model Perkins 1104C-44TAG (typical for this rating)
Engine type 4-cylinder, 4-stroke, turbocharged, air-to-air charge cooled, water-cooled diesel engine
Engine displacement 4.4 litres
Starting system 12V electric start
Cooling system radiator water cooling
Governor mechanical governor